06 · Result analysis
Recent tools
- Multi-selection table: column filters, asc/desc sorting, summary averages, and CSV export of the current view.
- EPS Profile: time-series chart for pressure/flow/velocity with min/max/delta in EPS mode.
Pressures
- Check the node table and sort by ascending pressure.
- Below-minimum pressure means poor service or intrusion risk.
- If many nodes are low, review sources (pumps/reservoirs) and trunk diameters.
Flows and velocities
- In the pipe table, sort by velocity or loss.
- Very high velocity → high losses and possible surge.
- Very low velocity → oversizing or dead zones.
Friction losses
- Use the pipe metric Headloss; find segments with highest loss per meter.
- Fix by increasing diameter, lowering roughness, or rerouting.
Problem hints
- Local low pressure: closed pipe, tight valve setpoint, or high elevation.
- Negative pressure: not enough energy; review pumps or levels.
- Slow convergence: loosen tolerances or validate with EPANET.
Quick checklist after a run
- Any nodes below threshold?
- Any pipe exceeding recommended velocity?
- Source levels/curves coherent?
- Units consistent with inputs?